A cooling tower rejects heat to the atmosphere by evaporating part of its water. The evaporated water is pure; the calcium, magnesium, silica and chloride stay behind. As the tower runs, the circulating water becomes a little more “concentrated” every day. If it is not managed properly, this turns into three problems that feed one another: scale, corrosion and biological fouling.
Why does tower water concentrate? Cycles of concentration and blowdown
The ratio of dissolved salts in the circulating water to those in the make-up water is called the cycles of concentration. To limit salt build-up, water is deliberately bled from the system (blowdown) and replaced with fresh water. As a first approximation, make-up demand equals evaporation plus blowdown plus drift losses.
Raising the cycles saves water. For the same cooling load, going from 3 to 6 cycles reduces make-up demand by roughly one fifth. But as cycles rise, hardness, alkalinity and chloride concentrate too, and the risk of scale and corrosion grows. In practice, four to six cycles is considered a good balance for many systems. The right target for your system is set by the make-up water chemistry and the treatment program applied.
1. Scale: the silent enemy of heat transfer
Calcium carbonate becomes less soluble as temperature rises, so scale builds up first on the hottest surfaces such as condensers and heat exchangers. Even a thin layer reduces heat transfer; condenser pressure and energy use go up and cleaning requires downtime. The scaling tendency of water can be predicted with indicators such as the Langelier Saturation Index (LSI).
Control: Scale inhibitors (antiscalants) delay crystal formation and distort the crystal structure so it cannot adhere to surfaces. Dispersants keep suspended particles dispersed. pH and cycle control complete the program. BiyoScale is our scale inhibitor developed for cooling towers.
2. Corrosion: shortening equipment life
Water in open towers is saturated with oxygen because it is in constant contact with air. High chloride and sulphate, low pH and the presence of mixed metals such as carbon steel, copper alloys and galvanised steel accelerate corrosion. Localised (pitting) corrosion under scale and biofilm is more dangerous than general thinning, because it perforates pipes unnoticed.
Control: Corrosion inhibitors form a protective film on the metal surface; copper alloys often need separate protection. Whether the program works is verified by measuring weight loss on corrosion coupons. For details, see our guide to choosing the right corrosion inhibitor.
3. Biological fouling and Legionella
Warm, aerated, sunlit tower water that carries nutrients is an ideal environment for bacteria, algae and fungi. Microorganisms form biofilm on surfaces. Biofilm reduces heat transfer, clogs the fill and causes microbiologically influenced corrosion underneath.
The most important public-health risk is Legionella. According to the World Health Organization’s guidance on Legionella, the bacterium grows at roughly 25–45 °C and fastest at 32–42 °C, which is the typical operating temperature of a cooling tower. Legionnaires’ disease can be contracted by inhaling droplets released from the tower. Biological control is therefore not only about efficiency but about human health.
Control: Regular biocide treatment, alternating oxidising and non-oxidising biocides to prevent resistance, dispersants that stop biofilm from attaching, shading the basin from sunlight, maintaining drift eliminators and removing dead legs where water stagnates. For microbiological control in cooling water we recommend BiyoCide.
How to build an effective program
- Know your water: hardness, alkalinity, conductivity, silica, chloride and pH in make-up and circulating water.
- Know your system: materials, temperatures, flow rates, dead zones and discharge limits.
- Set a target cycle: connect blowdown to an automatic, conductivity-controlled system.
- Design the chemicals together: scale inhibitor, corrosion inhibitor and biocide must be compatible.
- Measure and record: conductivity, pH, corrosion coupons, microbial counts and Legionella analysis.
Common mistakes
- Raising cycles to save water without checking the water analysis.
- Opening and closing the blowdown valve manually and irregularly.
- Using only a scale inhibitor and neglecting biological control.
- Using the same biocide for years.
- Restarting a tower that has been idle for a long time without disinfection.
Frequently asked questions
How often should cooling tower water be analysed?
Basic parameters such as conductivity and pH should be monitored continuously or daily. The frequency of detailed chemical analysis and microbial counts depends on system size and the risk assessment. Legionella testing follows the applicable regulations.
Does a scale inhibitor also prevent corrosion?
Not always. Some scale inhibitors give limited protection, but carbon steel and especially copper alloys usually need a separate corrosion inhibitor. We can define the right combination together based on your water analysis.
Do the same rules apply to closed cooling circuits?
In closed circuits evaporation and oxygen ingress are very limited, so corrosion control comes first. Scale and biological risk are lower but not zero; water losses and top-ups must always be monitored.
Conclusion
Managing cooling tower water well is one of the most effective ways to cut water, energy and maintenance costs at the same time. Scale, corrosion and biological fouling should be handled not separately but as parts of a single program.